How to Build a Rolling Offset in Autodesk Revit

Hagerman & Company

A rolling offset in Autodesk Revit is a diagonal run of pipe, duct, or conduit that connects two segments at different elevations, instead of stepping between them with separate vertical and horizontal runs. Revit doesn't have a single dedicated tool for this, but there are two reliable ways to build one: letting Revit use any elbow angle needed, or locking the layout to a specific, standard set of fitting angles. 

Note: The video below was recorded in an earlier version of Revit. The settings and technique shown are still current, though the video's reference to a "new" 2014 feature is now just historical context — see the note above. 

 

Why Rolling Offsets Are Tricky in Revit

Revit is naturally biased toward horizontal and vertical runs. If you sketch a segment and simply change elevation partway through, Revit typically breaks that into a vertical riser and a horizontal run rather than a single diagonal offset — which isn't always how you want the run to actually look or perform. Building a true rolling offset takes a deliberate technique, and which one you use depends on whether your trade or project standards call for exact fitting angles or not.

Both methods below work for conduit, and the same general approach applies to pipe and duct as well.

Before You Start: Isolate Your View

Before building the offset, it's worth isolating just the two segments you're connecting. Trying to navigate a full view while hunting for the right piece of conduit wastes time - using Revit's Temporary Isolate Element tool to hide everything else in the view makes the rest of this process much faster to work through.

Method 1: Unconstrained Elbow Angles

This method lets Revit calculate whatever angle is needed to connect the two segments, without restricting it to standard fitting angles.

  1. Go to Manage tab > Electrical Settings (or Mechanical Settings, depending on what you're routing).
  2. Under Angles, select Use any Angle.
  3. Select the open end of one segment, right-click the connector, and choose to draw conduit (or pipe/duct) toward the second segment.
  4. Before finishing the connection, check the Ignore Slope to Connect option. This forces Revit to angle the new segment and create the offset, rather than defaulting to separate vertical and horizontal pieces.

With this method, the resulting elbow angles will typically be non-standard values (for example, something like 20.7° rather than a round number). That's expected. This method prioritizes a fast, working connection over matching a specific fitting angle. If you or your fabricator can field-adjust to a non-standard bend angle, this is usually the quicker option.

Method 2: Specific, Standard Elbow Angles 

If your project or trade standards call for specific angles, 22.5° or 45° elbows, for example, use this method instead so Revit snaps to those standard values rather than calculating an arbitrary angle.

  1. Go to Manage tab > Electrical Settings (or Mechanical Settings).
  2. Under Angles, select Use Specific Angles, and confirm the angle set includes the values your standard requires (commonly 22.5°, 45°, and 90°).
  3. Sketch the run in plan view. Revit will snap the elbow angles to the closest value in your specified set as you draw.
  4. Align the segment to your starting reference point, then switch to an elevation view and select the full run.
  5. Use the Rotate tool, setting the base point to the center of the reference segment, and rotate the run to the angle you need. If Revit isn't snapping cleanly to the center point, typing SC overrides the snap to force a center-point selection.
  6. Use the Move tool (not drag) to bring the elbow up to its final connection point, and make sure Disjoin is unchecked so the run stays connected as you move it. Using Move instead of Drag helps avoid accidentally disconnecting the assembly during this step.

Which Method Should You Use?

  • Use Method 1 (Use any Angle + Ignore Slope to Connect) when speed matters more than matching a standard fitting angle, or when the resulting angle can be field-adjusted without issue.
  • Use Method 2 (Use Specific Angles) when your project standards, trade requirements, or fabrication process call for a defined set of fitting angles, such as 22.5° or 45° elbows.

Key Takeaways 

  • Revit has no single "rolling offset" tool, both methods here are workarounds built from existing settings and commands, not a dedicated feature.
  • Isolating your view first saves significant time versus navigating a full model to find the segments you need.
  • "Use any Angle" plus "Ignore Slope to Connect" is the fastest path to a working offset, at the cost of a non-standard elbow angle.
  • "Use Specific Angles" keeps your layout on standard fitting angles, but takes more manual rotating and aligning to get right.
  • Use Move, not Drag, when repositioning a connected run, to avoid accidentally disconnecting your segments.

FAQ: Revit Rolling Offsets

What is a rolling offset in Revit?

A rolling offset is a diagonal segment of pipe, duct, or conduit that connects two runs at different elevations in a single angled piece, rather than a separate vertical riser and horizontal run.

Does Revit have a built-in rolling offset tool?

No. Revit doesn't have one dedicated tool for this. Instead, it's created using a combination of the Electrical or Mechanical Settings angle controls, the Ignore Slope to Connect option, and standard editing tools like Rotate and Move.

Why are my elbow angles showing unusual values like 20.7°?

This happens when your Electrical or Mechanical Settings are set to "Use any Angle." Revit calculates whatever angle is needed to connect the two segments, which often isn't a round number. If you need standard angles like 22.5° or 45°, switch to "Use Specific Angles" instead.

Does this technique work for pipe and duct, or only conduit?

The same general approach applies to pipe, duct, and conduit. The Angles settings and Ignore Slope to Connect option are all available for each.


Need help standardizing your Revit MEP routing workflows?

If your team is working through Revit MEP routing challenges like this one, our Revit MEP training courses cover conduit, pipe, and duct workflows in depth. For firms setting project-wide fitting angle standards, our AEC/BIM consulting solutions can help build that into your standards from the start.

Browse Revit MEP training courses →

Submitted by Robert Levy, AEC Solutions Engineer, Hagerman & Company, Inc.